6 Service menu

Access the service menu by simultaneously pressing the

button and

button for approx. 3 seconds. All

relays and sensors can be controlled and checked in this

menu (refer to the system wiring manual included with

Fluropro).

6 Service / Diagnostics

Display

Relay check/sensor values

Test procedure

Collector pump test (array 1)

Collector pump 1 on, all other actuators off

Collector pump test (array 2 if applicable)

Collector pump 2 on, all other actuators off

Switching valve test

Switching valve on, all other actuators off

Legionella protection pump test

Legionella protection pump on, all other actuators

off

Cylinder reheat 230V demand test

Cylinder reheat 230V demand on, all other actua-

tors off

Cylinder reheat demand - volt free contacts test

Cylinder demand - volt free contacts - closed cir-

cuit, all other actuators off

Upper cylinder sensor value

Table 1 Actuators and sensors

The display returns to the main operating menu if you press

the

button and

button for 3 seconds. The relays

and sensors should be checked only by the installation and

service engineer.