Maintenance – Glow-worm Ultracom hxi User Manual

Page 28

Advertising
background image

0020107233_00 - 06/11 - Glow-worm

MAINTENANCE

- 28 -

13517

Diagram 11.3

SECURING

SCREW

(4 OFF)

CHASSIS FRONT

CONTROL BOX

SERVICE POSITION

13648

CASING
PANEL

INNER CASING
PANEL

SECURING
SCREWS (2 OFF)

SECURING
SCREWS

Diagram 11.2

1. Maximum Rate Check and Adjustment

noTe: To verify the maximum gas rate CO2 setting the

appliance must be checked at the maximum rate first.

Press the “reset” button on the controls fascia, release

and immediately press and hold in the “+” button. After

approximately 5 seconds “Hi” will be displayed. Pressing

the mode button when “Hi” is selected will force the boiler

to maximum rate, the display will flash between “Hi” and the

“default display” this will indicate the boiler has been forced to

maximum. Wait until the CO2 value is stable and check that

the value is within the range specified in table in the “check”

column.

If the combustion reading is not within the acceptable values

AND the integrity of the complete flue system and combustion

circuit seals have been verified and the inlet gas pressure

(and gas rate) have been verified, then, it will necessary to

adjust the combustion rate of the appliance.

noTe: adjustment is made by turning the gas valve

throttle an ⅛ of a turn, waiting 1 minute to allow the

appliance to stabilise before checking or making further

adjustments.

● Rotate the “throttle”(anti-clockwise to increase), to the

required CO2, refer to diagram 10.5 and the “SETTING”

column in the table.

● Exit the forced rate function, press the “mode” and “+”

buttons simultaneously, this will reset the boiler to the default

display. Now proceed to check the minimum rate adjustment.

2. Minimum Rate Check and Adjustment

● Now check the minimum gas rate CO2 setting: Press

and release the “reset” button on the controls fascia, then

immediately press and hold in either of the “+” buttons. After

approximately 5 seconds “Hi” will be displayed. Pressing the

“+” or “-” buttons will toggle between “Hi” and “Lo”. Press the

mode button when “Lo” is selected, this will force the boiler

to minimum rate and the display will flash “Lo”, indicating the

boiler is operating at minimum.

● Wait until the CO2 value is stable and check that the value

is within the range specified in table in the “check” column.

If adjustment is necessary, proceed as follows:

noTe: adjustment of the Co2 at minimum rate is very

coarse and should not be adjusted more than an ⅛ of

a turn at a time. Wait 1 minute to allow the appliance to

stabilise before checking or making further adjustments.

● Gradually rotate the “offset adjustment” (anti-clockwise to

decrease) to the required CO2, refer to diagram 10.5 and the

“SETTING” column in the table.

● Exit the minimum rate function, press the “mode” and “+”

buttons simultaneously, this will reset the boiler to the default

display.

3. Re-Check CO2 and check the CO/CO2

combustion ratio.

● Re-check the maximum and minimum CO2 values to

ensure that they are within the “setting” limits in the table

then check the CO/CO2 combustion ratio does not exceed

the value in the CO/CO2 column of the table. If the CO/CO2

setting exceeds the value in the table, a complete servicing of

the appliance will be necessary, refer to section 11.1.

If the CO2 and the CO/CO2 ratio falls within the tolerances

quoted, exit the function press the “mode” and “+” buttons

simultaneously, this will reset the boiler to the default display.

Remove the analyser probe and replace the cap on the

sampling point, replace the controls fascia, inner and front

casing panels.

IMPoRTanT: Remember to replace the sample point cap on

completion of the test.

GaS RaTe CHeCK

Check the gas rates as described in the commissioning section.

CoMPleTIon

If it is not possible to achieve the required results for either the

combustion or gas rates, it will be necessary to complete a full

service of the appliance and then repeat the combustion check

procedure. If after servicing and adjustment of the appliance

the combustion values are still unacceptable and after further

remedial work has been carried out, the appliance must be

disconnected until the CO/CO2 ratio is acceptable. Advice can

be sought from the Glow-worm Technical Helpline.

Advertising