Exhaust requirements, Electrical requirements – Labconco Biological Safety Cabinets 34608 Series User Manual

Page 9

Advertising
background image

Chapter 2: Prerequisites

Product Service 1-800-522-7658

4

Exhaust Requirements

If you intend to connect the Biosafety Cabinet to the optional Canopy
Connection Kit, first examine the location to ensure that it accommodates the
cabinet’s exhaust duct. The area directly above the cabinet’s exhaust port
should be clear of structural elements, water and utility lines, or other fixed
obstructions. There should be enough clearance to accommodate a 10-inch
diameter duct. Avoid cabinet locations that require an elbow directly above
the cabinet’s exhaust connection or an excessive number of elbows in the
exhaust system. For further information about the cabinet’s exhaust system
requirements, please refer to Chapter 3: Getting Started.

Electrical Requirements

The different Biosafety Cabinet models have the following electrical
requirements:

Model #

Requirements

3430000-3430009

115 VAC, 60 Hz, 12 Amps

3430800-3430809

115 VAC, 60 Hz, 12 Amps

3430820-3430829

230 VAC, 50/60 Hz, 6 Amps

3440000-3440009

115 VAC, 60 Hz, 12 Amps

3440800-3440809

115 VAC, 60 Hz, 12 Amps

3440820-3440829

230 VAC, 50/60 Hz, 6 Amps

3450000-3450009

115 VAC, 60 Hz, 16 Amps

3450800-3450809

115 VAC, 60 Hz, 16 Amps

3450820-3450829

230 VAC, 50/60 Hz, 8 Amps

3460000-3460009

115 VAC, 60 Hz, 16 Amps

3460800-3460809

115 VAC, 60 Hz, 16 Amps

3460820-3460829

230 VAC, 50/60 Hz, 8 Amps

All Biosafety Cabinets with model numbers ending in –00 to –09 are
designed for operation at 115 volts 60 Hz, alternating current. Biosafety
Cabinets with model numbers ending in –20 to –29 are designed for
operation at 230 +/- 20 volts, 50/60 Hz alternating current.

Note: A dedicated outlet with a circuit breaker rated at 20 amps should
be located as close as possible to the right rear side of the cabinet, at a
height even with, or higher than, the top of the bench or stand.

Note: On 115 VAC models, both electrical outlets are protected by a ground
fault interrupter circuit (GFIC). Labconco does not recommend plugging the
Biosafety Cabinet into a GFIC outlet.

Table 2-1

Advertising