LINK Systems OmniLink 5000 User Manual

Page 54

Advertising
background image

April 12, 2012

Manual Version 1.1

A.4

Now we go to the “Auto Sets” screen and with the RUN/PROG switch in PROG hit the “CONFIGURE”
softkey. After typing the configuration code, we press the “CONFIGURE AIR” softkey.

Since the hydraulic overload is wired in at “AS7", if the slot reported on the screen in not already
“AS7", we hit the “NEXT AIR SLOT” softkey until it is. The hardware detected should be “0 - 10 Volt
Out”.

The first thing we must configure is the “Name” of the system. The cursor should already be on the
“Name” line so we check to see if the name is already “Hydraulic Overload". If not, the “CHANGE
NAME” softkey allows us to cycle through the systems.

Using the arrow keys, we move the cursor to the “Transducer Type” line. Looking at table 4.1, we see
that the transducer type for any model pressure transducer with a 250 psi pressure range and a 4 to 20
ma output is “Type 3". We hit the “CHANGE TYPE” softkey select Type 3 from the list that appears.
When the proper type is selected, the “Air Pressure” line should change to read the pressure currently in
the hydraulic overload system.

Next we use the arrow keys to move the editing cursor to the “Maximum Pressure” line. From the
information we already gathered, we enter 80 psi.

Going to the “Minimum Pressure” line, we enter 20 psi.

“Max. Trip Point” should be the tonnage trip point at the Max Pressure (80 psi in this case) so we enter
400 tons. Note that units to the right of the number are also an editable parameter. When the editing
cursor is placed on the Max Trip Point units, we can press the “CHANGE UNIT” softkey to get a list of
supported units. The units can be pounds, kilograms, tons, or metric tons. A hydraulic overload will
typically use tons and that is what we select. Note that the units for minimum and maximum trip point
will always be the same, but will not necessarily be the same as the “Display Trip As” units. This
allows us to enter the minimum and maximum trip points in whatever units the name plate uses, but
operate the press in a different set of units.

“Min. Trip Point” should be the tonnage trip point at the Min Pressure ( 20 psi in this case) so we enter
100 tons.

The “Display Trip As” units we set to tons.

The “Fault Time” we leave at 20 seconds.

The “Valve Type” is set to “6". This value comes from table 4.2 for the type of servo valve we have.

The “Tolerance” is left at the default 2 psi.

Finally, we go back to the “Mode” line and use the “CHANGE MODE” softkey to toggle the mode to
“ON”. The “Auto Sets” operation screen can now be used to set the air pressure or trip tonnage. See
section 5.2 for operation details.

Section A.4

Example Linear Slide Adjust Configuration

This example assumes the linear slide adjust system has been wired to the option board at “SS1". First,

Advertising