5.26

The format to select a parameter status message is:

From PLC:

[LF]VS[PNUM]=[MNUM][CR]

where:

[PNUM]

is the two digit parameter number (with leading zero if necessary) .

[MNUM]

is the message number that is to be set for the line.

Reply From Link:

[LF]VSA[PNUM]=[MNUM][CR]

where:

[PNUM]

is the two digit parameter number (with leading zero if necessary) .

[MNUM]

is the message number that was set for the line.

It is strongly recommended that the PLC check the return reply to verify the message arrived correctly at
the OmniLink.