Product Specification and performance

8

DS-I 1-3k UPS User Manual

Battery

Voltage

36VDC

72VDC

72VDC

Current

31A max

30A max

35A max

Output

Voltage

110V/115V/120V/127Vac(120V Default)

Current

6.7A

12.5A

16.7A

Dimension

(W*D*H) mm

144*353*222

190*374*336

190*374*336

Weight (kg)

12

22

22

2. Electrical Performance

Input

Model

Voltage

Frequency

Power Factor

DS1000/2000/3000I

Single-phase

40-70Hz

>0.98(Full load)

3. Operating Environment

Temperature

Humidity

Altitude

Storage temperature

0

C-40

C

<95%

<1000m

-20

C-70

C

NOTICEIf the UPS is installed or used in a place where the altitude is above than 1000m,

the output power must be de-rated in use, please refer to the following:

Altitude (M)

1000

1500

2000

2500

3000

3500

4000

4500

5000

De-rating Power

100% 95%

91%

86%

82%

78%

74%

70%

67%

Output

Voltage

Regulation

Power

Factor

Frequency

tolerance.

Distortion

Overload capacity

Crest ratio

1%

0.9 lag

0.5% of

normal

THD<1%@Fu

ll Linear Load

THD<6%@Fu

ll nonlinear

load

130% load: transfers to

Bypass mode after 1

minutes

150% load: transfers to

Bypass mode after 0.5

minute

3:1

maximum

Advertising