Trouble Shooting

DS-I 1-3k UPS User Manual

49

Fault: Inverter fault

Inverter over voltage,

inverter under voltage,

Please contact with distributer or

service center.

51

Fault: UPS over

temperature

Environment

temperature is higher

than permitted point,

ventilation is blocked

Please ensure that nothing blocks

ventilation and environmental temp

must be 0~40

C

53

Fault: Fan failure

One or more fans are

failure, fan wires are

loosen

Please contact with distributer or

service center

55

Fault:

Inverter

overload

Loads are on inverter

and over the capacity

of the UPS

Remove some loads to ensure that

total loads is under the capacity of

the UPS

57

Fault:

Inverter

overload timeout

Load

is

over

the

capacity of the UPS

and timeout, UPS will

transfer

to

bypass

mode if bypass is

available

Remove some loads to under 95%,

UPS

will

transfer

to

inverter

automatically

65

Fault: Battery low

UPS works in battery

and battery voltage is

low

Recover input power or save data

upon “battery low”

71

Fault:

Charger

fault

There is no charger

output.

Please contact with distributer or

service center

72

Warn: input over

current

Abnormal large current

enter in rectifier.

Please contact with distributer or

service center

74

Warn:

Manual

shutdown

UPS

will

shutdown

output or transfer to

bypass mode

/

/

Battery discharge

time diminishes

The battery has not

been fully charged

Charge the battery for more than 10

hours

UPS is overload

Check the loads and remove some

devices

Battery aged

Replace

the

batteries.

Please

contact with distributer or service

center

to

obtain

replacement