Trouble Shooting

20

DS-I 1-3k UPS User Manual

20

Warn:

Bypass

voltage abnormal

Bypass voltage is out

of bypass range or is

off

Check if utility power is indeed out of

range.

24

Warn: Bypass over

load

Load is on bypass and

is overload

Remove some loads to ensure that

total loads is less than 95% of rated

capacity

26

Warn:

Bypass

overload timeout

Load is on bypass and

overload.

Overload

time is longer than the

overload capacity of

bypass.

UPS

will

shutdown output and

loads will loss power.

Remove some loads and restart

UPS again. When UPS is working

normally, turn on loads one by one.

30

Warn:

Transfer

times over limit in

1 hour

Transfer

times

between inverter and

bypass is over 5 in

recent 1 hour. UPS

works in bypass mode.

Check if output is overload or some

loads are shorted. Remove the

failure loads and restart the UPS or

wait

for

starting

inverter

automatically.

32

Warn:

output

shorted

Something shorted

Please remove all loads from UPS

output. Check if UPS output is

shorted. If not, please check all

loads.

34

Warn:

End

of

discharge

UPS works in battery

mode for long time

after utility failure. UPS

output will be off until

utility power is on.

Please save your data when UPS

alarm “utility fail”

38

Warn: Battery test

failure

Battery capacity is low

or load is low.

Please ensure that battery voltage is

higher than 36VDC and the load is

more than 30%.

47

Fault:

Rectifier

fault

Bus over voltage, bus

unbalance,

rectifier

starting failure, bus

under voltage, input

fuse is off

Please contact with distributer or

service center.