10. Trouble shooting

This section describes checking the UPS

’ status. This section also indicates various UPS

symptoms a user may encounter and provides a troubleshooting guide in the event the UPS

develops a problem. Use the following information to determine whether external factors

caused the problem and how to remedy the situation.

10.1 Checking UPS status

It recommended that checking the UPS operation status every six months.

Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an

alarm?

Check whether the UPS is operating in Bypass mode. Normally, the UPS operates

in Normal Mode. If it is operating in Bypass Mode, stop and contact your local

representative, or Channel Support.

Check whether the battery is discharging. When the utility input is normal, the

battery should not discharge. If the UPS is operating in Battery Mode, stop and

contact your local representative, or Channel Support.

10.2 Adjust the factors caused the problem

When the fault indicator is on, press FUNC button to see the fault code and warn code. Fault
and warn codes are

listed as following:

Code

Event

Possible cause

Solution

7

Battery

not

connected

Battery not connected

Check if battery switch is off or

battery cables are disconnected

10

EPO

Emergency power off

Short the EPO terminal 1&2 to

activate EPO

12

Inverter

capacity

not enough

16

Warn:

Input

voltage abnormal

Utility is failure

/

Input surge protector

opens

If utility is normal but rectifier is not

working, reset input surge protector

18

Warn: Line neutral

wires reversed/PE

not grounded

Input Line and neutral

is reversed

Check the polarity of line wire and

neutral wire

PE

wire

is

not

connected correctly in

UPS

Check if PE on input plug is shorted

with UPS rear panel. If not, contact

with distributer or service center. If

yes, please check PE wire in input

power socket