10

Compact IO

™

Universal Input module

3. Wiring the module
4. Configuring the module
5. Going through the startup procedure
6. Monitoring module operation

Step 1: Ensure that your 1769 system
power supply(1) has sufficient current
output to support your system configuration.

Reference

Chapter 3
(Installation and Wiring)

The modules maximum current draw is shown below

5V dc

24V dc

150 mA 45 mA

NOTE The module cannot be located more than 8 modules away from
the system power supply.

(1) The system power supply could be a 1769-PA2, -PB2, -PA4, -PB4, or the internal

supply of the MicroLogix 1500 packaged controller.

Step 2: Attach and lock the module.

Reference

Chapter 3
(Installation and Wiring)

NOTE The module can be panel or DIN rail mounted. Modules can be
assembled before or after mounting.