Chapter 2: Quick Start for Experienced Users

13

•

To ensures optimum accuracy, limit overall cable impedance by

keeping a cable as short as possible. Locate the module as close to
input devices as the application permits.

Grounding

!

ATTENTION! The possibility exists that a grounded or exposed

thermocouple can become shorted to a potential greater than that of the

thermocouple itself. Due to possible shock hazard, take care when wiring

grounded or exposed thermocouples. See Appendix D, Using Thermocouple

Junctions.

•

This product is intended to be mounted to a well-grounded mounting

surface such as a metal panel. Additional grounding connections from
the module’s mounting tabs or DIN rail (if used) are not required
unless the mounting surface cannot be grounded.

•

Keep cable shield connections to ground as short as possible.

•

Ground the shield drain wire at one end only. The preferred location is

as follows.
- For grounded thermocouples or millivolt sensors, this is at the sensor
end.
- For RTD and resistance sensors, this is at the module end.
- For insulated/ungrounded thermocouples, this is at the module end.
Contact your sensor manufacturer for additional details.

•

Refer to Industrial Automation Wiring and Grounding Guidelines,

Allen-Bradley publication 1770-4.1, for additional information.

The terminal connections for the CJC sensor are shown below: