Chapter 3: Installation and Wiring

25

Field Wiring
Connections
System Wiring
Guidelines

Consider the following when wiring your system:

General

•

Power and input wiring must be in accordance with Class 1, Division

2 wiring methods, Article 501-4(b) of the National Electric Code,
NFPA 70, and in accordance with the authority having jurisdiction.

•

Channels are isolated from one another by ±10 Vdc maximum.

•

Route field wiring away from any other wiring and as far as possible

from sources of electrical noise, such as motors, transformers,
contactors, and ac devices. As a general rule, allow at least 15.2 cm
(6 in.) of separation for every 120V of power.

•

Routing field wiring in a grounded conduit can reduce electrical noise.

•

If field wiring must cross ac or power cables, ensure that they cross

at right angles.

•

If multiple power supplies are used with analog millivolt inputs, the

power supply commons must be connected.

•

Provision shall be made to prevent the rated voltage being exceeded

by the transient disturbances of more than 40%.

•

The system shall be mounted in an ATEX certified enclosure with a

minimum ingress protection rating of at least IP54 as defined in
IEC60529 or EN60529 and used in an environment of not more than
pollution degree 2.

•

Earthing is accomplished through mounting of modules on rail.

•

Subject devices are for operation in Ambient Temperature Range: 0 C

to +60 C

Terminal Block

•

Do not remove the CJC sensor from the terminal block if

thermocouples are to be utilized. Removal of the sensor will reduce
accuracy.

•

For millivolt and current sensors, use Belden 8761 shielded,

twisted-pair wire (or equivalent) to ensure proper operation and high
immunity to electrical noise.

•

For RTD and resistance sensors, use Belden 9501 (2 wire), 9533 (3

wire) and 83503 ( for runs over 100 feet) or equivalent.

•

For a thermocouple, use the shielded, twisted-pair thermocouple

extension lead wires specified by the thermocouple manufacturer.