Step 3: Wire the module.

Reference

Chapter 3
(Installation and Wiring)

Follow the guidelines below when wiring the module.

General

• Power and input wiring must be in accordance with Class 1, Division

2 wiring methods, Article 501-4(b) of the National Electric Code,
NFPA 70, and in accordance with the authority having jurisdiction.

• Channels are isolated from one another by ±10V dc maximum.

• Route field wiring away from any other wiring and keep it as far as

possible from sources of electrical noise, such as motors,
transformers, contactors, and ac devices. As a general rule, allow at
least 15.2 cm (6 in.) of separation for every 120V of power.

• Routing field wiring in a grounded conduit can reduce electrical noise.

• If field wiring must cross ac or power cables, ensure that they cross

at right angles.

• If multiple power supplies are used with analog millivolt inputs, the

power supply commons must be connected.

Terminal Block

•

Do not remove the CJC sensor from the terminal block if

thermocouples are to be utilized. Removal of the sensor will reduce
accuracy.
Note: For improved accuracy, use a remote terminal block
configuration when possible. See chapter 3 for more details.

•

For millivolt and current sensors, use Belden 8761 shielded, twisted-

pair wire (or equivalent) to ensure proper operation and high immunity
to electrical noise.

•

For RTD and resistance sensors, use Belden 9501 (2 wire), 9533 (3

wire) and 83503 ( for runs over 100 feet) or equivalent.

•

For a thermocouple, use the shielded, twisted-pair thermocouple

extension lead wires specified by the thermocouple manufacturer.
Using the incorrect type of thermocouple extension wire or not
following the correct polarity will cause invalid readings.