Spectrum Controls 1746sc-NI8u User Manual

Page 28

Advertising
background image

16

SLC 500

Universal Analog Input Module

transformers, contactors, and ac devices. As a general rule, allow at
least 6 in. (about 15.2 cm) of separation for every 120 V of power.

• Routing the field wiring in a grounded conduit can reduce electrical

noise further.

• If the field wiring must cross ac or power cables, ensure that they cross

at right angles.

• To limit the pickup of electrical noise, keep thermocouple, RTD,

millivolt, and milliamp signal wires as far from power and load
lines as possible.

• For improved immunity to electrical noise, use Belden 8761

(shielded, twisted pair) or equivalent wire for millivolt sensors; or
use shielded, twisted pair thermocouple extension lead wire
specified by the thermocouple or RTD manufacturer. Using the
incorrect type of thermocouple extension wire or not following the
correct polarity may cause invalid readings.

• There is one shield pin for every two input channels. All shields

are internally connected, so any shield terminal can be used with
any channel.

• Ground the shield drain wire at only one end of the cable. The

preferred location is at the shield connections on the terminal
block. (Refer to IEEE Std. 518, Section 6.4.2.7 or contact your
sensor manufacturer for additional details.)

• Keep all unshielded wires as short as possible.

• To limit overall cable impedance, keep input cables as short as

possible. Locate your I/O chassis as near the RTD or
thermocouple sensors as your application will permit.

• Tighten screw terminals with care. Excessive tightening can strip

a screw.

• Follow system grounding and wiring guidelines found in your

SLC 500 Installation and Operation Manual.

Wiring RTD or

Resistance Sensors

to the NI8u Module

The NI8u module supports two, three, and four wire RTDs or
resistance inputs connected individually to the module (channels 4
through 7), as shown in the figure below.

Advertising