Spectrum Controls 1746sc-NI8u User Manual

Page 95

Advertising
background image

Appendix A: Module Specifications

83

The following table provides the maximum error for each RTD and
resistance type when the 10 Hz, 50 Hz, and 60 Hz filters are used and the
module is operating at 0°C to 60°C and was at that temperature. Errors
due to lead wire resistance mismatches are not included.

Input

Max. Error

Type

0°C to 60°C

100

Ω

Pt 385

±3.3°C

200

Ω

Pt 385

±2.8°C

500

Ω

Pt 385

±3.0°C

1000

Ω

Pt 385

±2.9°C

100

Ω

Pt 3916

±2.7°C

200

Ω

Pt 3916

±2.4°C

500

Ω

Pt 3916

±2.3°C

1000

Ω

Pt 3916

±2.2°C

10

Ω

Cu 426

±4.5°C

120

Ω

Ni 618

±0.8°C

120

Ω

Ni 672

±0.8°C

3000

Ω

Resistance

±7.0

Ω

The diagrams that follow provide data from a sample module for a given
RTD type over a range of inputs, over temperature.

100

Ω

Pt 385 RTD, Example Deviations

-1.4

-1.3

-1.2

-1.1

-1

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0

0.1

-200 -100

0

100

200

300

400

500

600

700

800

900

Degrees C RTD Input

Degrees C Deviation

Ch 7 Delta, 25C

Ch 7 Delta, 0C

Ch 7 Delta, 60C