Spectrum Controls 1746sc-NI8u User Manual

Page 64

Advertising
background image

52

SLC 500

™

Universal Analog Input Module

Procedure

1. Using the memory map function, create integer file N10. Integer file

N10 should contain eight elements (N10:0 through N10:7).

2. Using the APS software data monitor function, enter the

configuration parameters for all eight universal channels into a source
integer data file N10.

Figure 5.2

Data table for initial programming

address 15

data

0

address

15

data

0

N10:0

0000

0010

0010

0011

N10:3

0000

0010

0010

0011

N10:4

0000

0010

0010

0011

N10:5

0000

0010

0010

0011

N10:6

0000

0010

0010

0011

N10:7

0000

0010

0010

0011

Press a key or enter value

N10:3/0 = 1

offline

no forces

binary data

decimal addr

File EXMPL

CHANGE

RADIX

F1

SPECIFY

ADDRESS

F5

NEXT

FILE

F7

PREV

FILE

F8

3. Program a rung in your ladder logic to copy the contents of integer

file N10 to the eight consecutive output words of the universal
module beginning with O:3.0.

Figure 5.3

Initial programming example

First Pass Bit

s:1

] [

15

COP

COPY FILE

Source #N10:0

Length 8

Dest #O:3.0

Initialize Module

On power up, bit S:1/15 is set for the first program scan, and integer file N10
is sent to the NI8u channel configuration words.