Safety features, Block diagram/terminal configuration – Pilz PZE X4VP8 24VDC 4n/o User Manual
Page 6

PZE X4VP8
Operating Manual PZE X4VP8
1003206EN06
6
Safety features
The unit meets the following safety requirements:
}
The contact expander module expands an existing circuit. As the output relays are
monitored via the base unit's feedback loop, the safety functions on the existing circuit
are transferred to the contact expander module.
}
The safety function remains effective in the case of a component failure.
}
Earth fault in the feedback loop:
Detected, depending on the base unit that is used.
}
Earth fault in the input circuit:
The output relays deenergise and the safety contacts open.
Block diagram/terminal configuration
8A
6B
7B
5B
8B
5A
6A
7A
Delay
*
*Insulation between the nonmarked area and the relay contacts: Basic insulation (over
voltage category III), Protective separation (overvoltage category II)