1 safety characteristic data, Safety characteristic data – Pilz PNOZ m EF 2MM User Manual
Page 23

Technical details
Operating Manual PNOZ m EF 2MM
1003107EN01
23
8.1
Safety characteristic data
Operating
mode
EN ISO
138491:
2008
PL
EN ISO
138491:
2008
Category
EN IEC
62061
SIL CL
EN IEC
62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
138491:
2008
T
M
[year]
Monitoring 1
encoder
PL d
Cat. 2
SIL CL 2
1,80E08
SIL 2
1,58E03
20
Monitoring 2
encoder
PL e
Cat. 3
SIL CL 3
1,01E09
SIL 3
8,41E05
20
Monitoring
safe en
coder
PL e
Cat. 4
SIL CL 3
2,35E09
SIL 3
2,04E04
20
–
PL e
Cat. 4
SIL CL 3
3,37E10
SIL 3
2,88E05
20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.