1 safety characteristic data, Safety characteristic data – Pilz PSSu H F PN User Manual
Page 20

Technical Details
Operating Manual PSSu H F PN
22071-EN-06
20
Environmental data
312043
Airgap creepage
In accordance with the standard
EN 60664-1
Overvoltage category
II
Pollution degree
2
Protection type
Mounting (e.g. cabinet)
IP54
Housing
IP20
Mechanical data
312043
Material
Bottom
PC
Front
PC
Dimensions
Height
128,4 mm
Width
75,2 mm
Depth
79,4 mm
Weight
199 g
Safety characteristic data
Operating
mode
EN ISO
13849-1:
2008
PL
EN ISO
13849-1:
2008
Category
EN IEC
62061
SIL CL
EN IEC
62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2008
T
M
[year]
–
PL e
Cat. 4
SIL CL 3
2,88E-09
SIL 3
3,95E-05
20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
Information
A safety function's SIL/PL values are
not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.
8.1