Pilz PSSu E F INC User Manual
Page 29
Advertising

Wiring
Operating Manual PSSu E F INC(T)
1001454EN07
29
–
Inputs/outputs on the counter modules: 1.5 mm
2
(AWG16)
–
Analogue inputs/outputs: 1.5 mm
2
(AWG16)
–
Communication cables: 1.5 mm
2
(AWG16)
–
Test pulse outputs: 1.5 mm
2
(AWG16)
–
Power supply: 2.5 mm
2
(AWG12)
–
Functional earth: 2.5 mm
2
(AWG12)
}
On base modules with screw terminals:
–
If you use a multistrand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
2
, Form A or C,
although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 609471, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.
–
Maximum torque setting: 0.8 Nm
}
Use copper wiring.
Advertising
This manual is related to the following products: