4 function description, 1 module features, 1 function description – Pilz PSSu E AI SHT2 User Manual
Page 11: Section 4, Function description, Module features, 4function description

Function Description
Operating Manual PSSu E AI SHT2
1003113EN01
11
4
Function Description
4.1
Module features
4.1.1
Function description
The electronic module PSSu E AI SHT2 contains two shunts for scaling an input current I
I0
(connection I0). The two current outputs I
O0
(connection O0+) and I
O1
(connection O1+) are
evaluated by analogue current inputs.
Scaling is applied during evaluation via an analogue input module with an input resistance
of 115 Ohm, (e.g. PSSu E F AI I)
}
Scaling factor with resistance R
1
+ R
2
= 10,150 Ohm (connections O0+/O0):
I
O0
: I
I0
= 1:10
}
Scaling factor with resistance R
2
= 6,750 Ohm (connections O1+/O1):
I
O1
: I
I0
= 1:20
The maximum output variable error at 25 C is:
}
When two analogue input modules are connected (e.g. PSSu E F AI I) 1,0 %
}
When one analogue input module is connected (e.g. PSSu E F AI I) 3,6 %
Example:
}
Input current I
I0
= 200 mA
}
Output current I
O0
at R
1
+ R
2
= 20 mA
}
Output current I
O1
at R
2
= 10 mA
I 0
O 0 +
O 1 +
0 V
O 0 -
O 1 -
I O1
I O0
I I0
R 1
R 2