Wiring

Operating Manual PSSu E S 2AI RTD(­T)
22017­EN­06

26

6

Wiring

6.1

General wiring guidelines

Please note:

}

The supply voltages for actuators and sensors must be extra low voltages with protect­
ive electrical separation (PELV or SELV) in accordance with VDE 0100, Part 410. Fail­
ure to do so could result in electric shock.

}

We recommend that you use shielded signal lines.

}

On base modules with C­rail:

–

Connect the shield to the terminals on the C­rail.

–

Connect the C­rail with low impedance to the functional earth.

}

On base modules without C­rail:

–

Connect the shield as shown in the terminal configuration section.
The module connects the shield to the mounting rail.

–

Connect the mounting rail to the functional earth via an earthing terminal.

}

In environments with strong EMC interference, base modules without a C­rail provide
better protection if the shield is connected.

}

Use copper wiring.

}

The terminal configuration as stated on the front plate applies for base modules with C­
rail. The terminal configuration as stated in the technical documentation applies for all
other base modules.

6.1.1

Mechanical connection of the base modules

Procedure:

}

Use a flat blade screwdriver (DIN 5264­A)!

DIN 5264-A

}

Strip the wire back 8 mm.

}

If necessary, label the connection level with a colour marker [3].

}

Base module with screw terminals:

–

Use a screwdriver to loosen the screw on the screw terminal [1]

–

Insert the stripped cable into the round fixing hole [2], as far as it will go.

–

Tighten up the screw on the screw terminal.