Terminal configuration, 6wiring, 2 terminal configuration – Pilz PSSu E PS-P +/-10V User Manual
Page 25

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-3
6.2
Terminal configuration
6
Wiring
6.2
Terminal configuration
6200
Terminal configuration
6-
][Klemmenbelegung PS-P 10V
Base module
Terminal configuration
Screw terminals:
PSSu BP 1/8S
PSSu BP 1/8S-T
Cage clamp terminals:
PSSu BP 1/8C
PSSu BP 1/8C-T
Without C-rail:
11-21: 0 V extraction
(11-21 linked internally)
12-22: 0 V infeed
(12-22 linked within the base module)
13-23: +24 V infeed
(13-23 linked within the base module)
14: -10 V extraction
24: +10 V extraction
Screw terminals:
PSSu BP 1/12S
PSSu BP 1/12S-T
Cage clamp terminals:
PSSu BP 1/12C
PSSu BP 1/12C-T
Without C-rail:
11-21: 0 V extraction
(11-21 linked internally)
12-22: 0 V infeed
(12-22-15-25 linked within the base
module)
13-23: +24 V infeed
(13-23-16-26 linked within the base
module)
14: -10 V extraction
24: +10 V extraction
15-25: 0 V infeed
(12-22-15-25 linked within the base
module)
16-26: +24 V infeed
(13-23-16-26 linked within the base
module)
21
11
22
12
23
13
24
14
21
11
22
12
23
13
24
14
26
16
25
15