Air for combustion and ventilation, Continued, Ventilation air – Desa VF-24N-MHD User Manual

Page 7

Advertising
background image

www.desatech.com

116986-01B



aIR FoR CoMBUsTIoN

aNd VeNTIlaTIoN

Continued

If the actual Btu/Hr used is less than the maximum

Btu/Hr the space can support, the space is an uncon-

fined space. You will need no additional fresh air

ventilation.

WARNING: If the area in

which the heater may be oper-

ated is smaller than that defined

as an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining

unconfined space, you must provide two permanent

openings: one within 12" of the ceiling and one

within 12" of the floor on the wall connecting the

two spaces (see options 1 and 2, Figure 2). You

can also remove door into adjoining room (see

option 3, Figure 2). Follow the National Fuel Gas

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for

Combustion and Ventilation for required size of

ventilation grills or ducts.

Figure 2 - Ventilation Air from Inside

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills

Into Adjoining

Room,

Option 1

12"

12"

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or

ducts. You must provide two permanent openings:

one within 12" of the ceiling and one within 12"

of the floor. Connect these items directly to the

outdoors or spaces open to the outdoors. These

spaces include attics and crawl spaces. Follow the

National Fuel Gas Code, ANSI Z223.1/NFPA 54,

Section 5.3, Air for Combustion and Ventilation for

required size of ventilation grills or ducts.
IMPORTANT:

Do not provide openings for inlet

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic

will activate the power vent.

Figure 3 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic

Outlet

Air

Inlet

Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic