Reclosing device by insulation, m mode – CIRCUTOR REC3 Series User Manual

Page 18

Advertising
background image

Figure 12: REC 3 in automatic mode, with mode selector switch at ON�

The

REC 3 allows two modes of

automatic reclosing

:

-

M Mode, by insulation, (REC 3 of 30 mA) the unit does not reclose until the leakage

has disappeared.

-

T Mode, by time, (REC 3 of 300 mA) the unit reclose the system, independently of the

leakage.

5�2�1�- RECLOSING DEVICE BY INSULATION, M MODE

Following a time delay after a disconnection due to an RCCB trip, the

REC 3 makes a measure-

ment to check whether there is a leakage current. If there is none it begins to reclose.

The

REC 3 attempts a maximum of 3 measurements to check the leakage current; following

this the unit stays locked and does not automatically reclose.

If the time between a reclosure and the next trip is greater than the restart time, the reclosing

attempts start over at zero.

The delay and restart times depend on the number of attempts the reclosing device has made,

as shown in

Table 3

Table 3: Delay and Restart Times�

Reclosures

1

2

3

Delay

Restart

Delay

Restart

Delay

Restart

REC3

<3 sec.

10 sec.

20 sec.

20 sec.

180 sec.

60 sec.

The leakage current will be supervised by measuring the resistance downstream of the

tripped RCCB.

18

Instruction Manual

REC 3 - REC 3C