REGULADOR DE ENERGÍA REACTIVA DIR2

El DIR2 es un regulador de un solo paso de muy reducidas
dimensiones, ideal para compensar el cos

ϕ

en instalaciones

que requieren una regulación en un solo escalón. Puede
emplearse también como complemento de un regulador de
más pasos, ya sea como relé de alarma o para conectar un
paso adicional.

DIR2 PF Regulator

The DIR2 is a PF regulator to control a single capacitor step. The
DIR2 is the ideal regulator for cos

ϕ

compensation in small

installations where a single step regulation is required. The
regulator can be also used as alarm relay in case of lack of
compensation or as additional step in an existing capacitor bank.

CONEXIÓN Y AJUSTES

Para la conexión y puesta en marcha del relé DIR2, deben
tenerse en cuenta los siguientes puntos :
- El relé DIR2 requiere la instalación de un transformador de
corriente eficiente de la serie MC1 (In / 0,25 A)
, donde In
debe ser mayor que la intensidad total de los receptores
instalados en la línea a compensar.
- El transformador de corriente se instalará en un punto de la
acometida por el que circule la totalidad de la intensidad de la
línea a compensar, pero sin leer la intensidad propia del
condensador (ver fig.1).
- Conectar el secundario del transformador de corriente (entre
borne 1S1 y borne 1S2, 2S1 ó 2S2, según el valor de primario
de corriente adecuado a la máxima corriente de la instalación)
en los bornes señalizados como S1 y S2 en el DIR2.
- La tensión de alimentación del regulador DIR2 debe tomarse
entre fases (habitualmente entre las fases L2 y L3) y debe
conectarse a los bornes A1-A2.
- IMPORTANTE: La fase donde está instalado el
transformador de intensidad, (normalmente L1), no debe
coincidir
con las fases de las que se toma la tensión de
alimentación (normalmente L2-L3).
- La intensidad reactiva de disparo del relé se fija en el mando
frontal. El relé conecta cuando la intensidad reactiva medida
supera el valor marcado. Para evitar fluctuaciones en la
operación, el relé desconecta cuando la intensidad reactiva
medida baja por debajo del 70% de dicho valor.
- Si el relé no conecta y hay carga suficiente en la instalación,
revisar las conexiones, y si son correctas, probar a
intercambiar entre sí las conexiones que van a los terminales
S1 y S2 del DIR2.

CONNECTION AND SETUP

To connect the DIR2 PF regulator, the following steps must be
considered:
- The DIR2 regulator requires one efficient current transformer
of MC1 type (In / 0.25 A)
. The primary current In must be
greater than the maximum current expected at the load to be
compensated.
- The current transformer must be placed in the line supplying
the load to be compensated. It must measure the load current,
excluding the capacitor current (see fig. 1)
- Connect the CT secondary terminals (between terminal 1S1
and terminal 1S2, 2S1 or 2S2, with the primary side value fitted
to the maximum value of the current drawn by the loads) to the
DIR2 terminals designated as S1-S2.
- The supply voltage of the DIR2 regulator must be taken phase
to phase (usually from phases L2 and L3) and connected to
terminals A1-A2).
- IMPORTANT: The phase where CT is placed (usually L1)
must not coincide with any of the phases used for the regulator
supply (usually L2 and L3)
- The reactive current at which the regulator trips is set by means
of the frontal knob. The output relay is activated when the
measured reactive current exceeds the set value. To avoid relay
flickering, the relay is deactivated when the current goes below
the 70% of the set value.
- If the DIR2 relay does not connect when it is expected,
(considerable reactive current at the load), review the
connections and check if it connects when reversing the
connections of CT secondary side to S1-S2 terminals.

CARACTERISTICAS TÉCNICAS / TECHNICAL CHARACTERISTICS

Tensión de alimentación : Fase - Fase

400 V ±10%

Supply voltage : Phase to Phase

Frecuencia

50-60 Hz

Frequency

Consumo

< 3 VA

Power consumption

Circuito de intensidad

Current circuit

Corriente nominal

0,25 A c.a. / a.c.

Rated current

Sobrecarga permanente

1,2 In

Maximum permanent overload

Consumo

< 0,05 VA

Power consumption

Corriente reactiva de disparo

Reactive tripping current

Margen de ajuste del disparo: C/K

0,15 ... 2

Ver ejemplo / See example

Tripping adjustment range: C/K

Retardo de conexión Tc

5 s

Connection delay Tc

Retardo de desconexión Tr

2 s

Disconnection delay Tr

Relé de salida

Output relay

Corriente térmica Ith

10 A

Thermal current Ith

AC11 Ie / Ue

10 A / 250 V c.a. / a.c.

AC11 Ie / Ue

DC11 Ie / Ue

0,3 A / 110 V c.c. / d.c

DC11 Ie / Ue

Vida mecánica

10

10

6

maniobras / operations

Mechanical endurance

Vida eléctrica

10

10

4

maniobras / operations

Electrical endurance

Condiciones ambientales

Environment conditions

Temperatura de trabajo

-10º a +50 ºC

Working temperature

Humedad relativa máxima sin condensación

95 %

Maximum relative humidity without condensation

Altitud máxima de funcionamiento

2000 m (s.n.m.) / 2000 m (AMSL) Maximum operation altitude

Otras características:

Other characteristics

Indicación de conexión:
Verde: Alimentación, Rojo: Relé conectado

LED: Verde / Rojo

Green / Red LED

Connection indication:
Green : Supply, Red: Relay ON

Fijación sobre perfil

DIN 46277 (EN 50022)

Rail fastening

Categoría de protección de la caja

IP 40

Enclosure protection category

Peso

0,25 kg

Weight

Protección al choque eléctrico

doble aislamiento clase II /

class II double isolation

Electric shock protection