R7C112 FAR5-Q8-525-400

400

8

7 x 75

820

280

140

FR8

R7C113 FAR5-Q12-562.5-400

400

8

37.5 + (7 x 75)

878

300

150

FR12

R7C114 FAR5-Q12-600-400

400

8

8 x 75

937

320

160

FR12

R7C115 FAR5-Q12-637.5-400

400

9

37.5 + (8 x 75)

996

340

170

FR12

R7C116 FAR5-Q12-675-400

400

9

9 x 75

1054

360

180

FR12

R7C117 FAR5-Q12-712.5-400

400

10

37.5 + (9 x 75)

1113

380

190

FR12

R7C118 FAR5-Q12-750-400

400

10

10 x 75

1171

400

200

FR12

Table 2.- Standard filters for 60 Hz systems

Q

CODE

TYPE (*)

VOLTAGE STEPS

STEPS x (kvar)

Irms

5

th

7th CABINET

(V)

(A) (A) (A)

R7C401 FAR5-Q6-105-400 480 3

3 x 35

166

60

30

FR6

R7C402 FAR5-Q6-140-400 480 4

4 x 35

221

80

40

FR6

R7C403 FAR5-Q6-175-400 480 5

5 x 35

276

100

50

FR6

R7C404 FAR5-Q6-210-400 480 6

6 x 35

331

120

60

FR6

R7C405 FAR5-Q6-245-400 480 4

35 + (3 x 35)

387

140

70

FR6

R7C406 FAR5-Q6-280-400 480 4

4 x 70

442

160

80

FR6

R7C407 FAR5-Q6-315-400 480 5

35 + (4 x 70)

497

180

90

FR6

R7C408 FAR5-Q6-350-400 480 5

5 x 70

552

200

100

FR6

R7C409 FAR5-Q8-385-400 480 6

35 + (5 x 70)

608

220

110

FR8

R7C410 FAR5-Q8-420-400 480 6

6 x 70

663

240

120

FR8

R7C411 FAR5-Q8-455-400 480 7

35 + (6 x 70)

718

260

130

FR8

R7C412 FAR5-Q8-490-400 480 8

7 x 70

773

280

140

FR8

R7C413 FAR5-Q12-525-400 480 8

35 + (7 x 70)

829

300

150

FR12

R7C414 FAR5-Q12560-400 480 8

8 x 70

884

320

160

FR12

R7C415 FAR5-Q12-595-400 480 9

35 + (8 x 70)

939

340

170

FR12

R7C416 FAR5-Q12-630-400 480 9

9 x 70

994

360

180

FR12

R7C417 FAR5-Q12-665-400 480 10

35 + (9 x 70)

1050

380

190

FR12

R7C418 FAR5-Q12-700-400 480 10

10 x 70

1105

400

200

FR12

1.3.- Safety warnings

This manual contains information and warnings about the FAR-Q hybrid
bank which must be followed to guarantee the proper operation of all
instrument functions and to maintain it in a safe condition.

If the instrument is not installed in accordance with manufacturer's

specifications, the instrument's protection may be damaged.

Check that the protection devices are operating correctly.

2.- MAIN FEATURES

A FAR-Q hybrid filter is formed by various groups of inductances plus a capacitor in
series, located in an appropriate cabinet. Each step is characterised by three
parameters:
1) Power factor to be corrected at 50 or 60 Hz.
2) Harmonic to be filtered, generally 5