6installation – United States Stove Company 5040 User Manual

Page 8

Advertising
background image

6

INSTALLATION

COMBUSTION AIR SUPPLY

For a mobile home installation the stove must be connected to an

outside source of combustion air. A 2” inside diameter metallic pipe,

either flexible or rigid, may be attached to the inlet at the stove’s

rear (refer to figure 5a.) A rodent guard (minimum ¼” wire mesh)/

wind hood must be used at the terminus (refer to figure 7). All con-

nections must be secured and airtight by either using the appropri-

ately sized hose clamp and/or UL-181-AP foil tape.

For mobile home installations only: 2” inside diameter pipe may

be used for the first 5 feet of combustion air supply run. From 5 to

10 feet use 2 ¾” inside diameter pipe. No combustion air supply

may exceed 10 feet.

Sources of Outside Combustion Air

a. For freestanding installations

• A hole in floor near stove rear terminating only in a venti

lated crawl space.

• A hole in the wall behind the stove.

WHEN OUTSIDE AIR IS NOT USED

If outside air is not used, it is important that combustion air is eas-

ily available to the air inlet. A closeable outside air register can

be used in tightly insulated homes. In insert installations, flashing

vents should not be restricted. The flashing should not necessarily

seal the fireplace face.

VENTING

This freestanding appliance is certified for use with listed TYPE L-

Vent, 3” or 4” diameter in size. The stove was tested with Simpson

Duravent brand. Class “A” chimney is not required. Refer to the

instructions provided by the vent manufacturer, especially when

passing through a wall, ceiling or roof.

This is a pressurized exhaust system. All vent connector joints

must be sealed with 500

O

F (260

O

C) RTV silicone sealant to ensure

consistent performance and avoid smoke spillage. All horizontal

connector joints must be sealed with UL-181-AP foil tape. We rec-

ommend that all vertical vent connector joints be secured with a

minimum of 3 screws.

It is strongly recommended that you have a minimum of 6’ of ver-

tical pipe in your exhaust system. For best performance of the

stove limit the number of elbows and horizontal pipe as much as

possible.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING

ANOTHER APPLIANCE.

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING

SYSTEM OF THIS UNIT.

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANU-

FACTURER.

21 1/2”

EXHAUST

PIPE

AIR

INLET

PIPE

28 1/2”

11”

6 1/2”

10 3/4”

FIGURE 5a

5 7/8”

FIGURE 7

24 3/4”

TRIM

COLLAR

28 1/2”

RODENT

GUARD

VENTILATED

CRAWL SPACE

Advertising