Installation

(for qualified installers only)

Travis Industries

4 0 7 0 6 2 0

100-01188_000

Rear Vent Configuration with Horizontal Termination (with vertical
rise)

•

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.

•

Up to four elbows (45

°

or 90

°

) may be used.

•

Only one horizontal elbow may be used.

5 feet

0 feet

0 feet

5 feet

0 feet

20 feet

20 feet

5 feet

10 feet

5 feet

10 feet

0 feet

15 feet

20' (max)

10 feet

15 feet

15 feet

20' (max)

10 feet

15 feet

22' (max)

22' (max)

Exhaust Restrictor # 6

Intake Restrictor # 2
Diffuser Position # 2

Exhaust Restrictor # 2
Intake Restrictor # 1 (stock)

Diffuser Position # 1 (stock)

Exhaust Restrictor # 4

Intake Restrictor # 2
Diffuser Position # 2

This is considered a horizontal

elbow (it does not matter

whether it turns right or left).

It may be a 90° or 45° elbow.

This is considered a

vertical elbow

Horizontal length is calculated by adding

both lengths of horizontal run

(Horizontal Length = H1 + H2).

H1

H2