Installation – Desa VSGF33NRC User Manual

Page 12

Advertising
background image

www.desatech.com

119304-01A

1

INSTALLATION

Continued

13"

16"

19"

21"

2

1

/

2

"

6"

8"

10"

Minimum Non-
Combustible
Material

Figure 16 - Minimum Mantel Clearances

for Built-In Installation

Mantel Shelf

Note:
All Vertical
measurements
are from top of
fireplace opening
to bottom of
mantel shelf.

Mantel Clearances for Built-In
Installation

If placing mantel above built-in fireplace, you must

meet minimum clearance between mantel shelf and

top of fireplace opening.

NOTICE: If your installation does

not meet the minimum clear-

ances shown, you must do one

of the following:

• raise the mantel to an accept-

able height

• remove the mantel

NOTICE: Surface temperatures

of adjacent walls and mantels

become hot during operation.

Walls and mantels above the

firebox may become hot to

the touch. If installed properly,

these temperatures meet the

requirement of the national

product standard. Follow all

minimum clearances shown in

this manual.

INSTALLING GAS PIPING TO
FIREPLACE LOCATION

WARNING: This appliance

requires a 1/2" NPT (National

Pipe Thread) inlet connection to

the pressure regulator.

WARNING: A qualified

service person must connect

fireplace to gas supply. Follow

all local codes.

CAUTION: Never connect pro-

pane/LP fireplace directly to the

propane/LP supply. This fireplace

requires an external regulator

(not supplied). Install the external

regulator between the fireplace

and propane/LP supply.

WARNING: Never connect

natural gas fireplace to private

(non-utility) gas wells. This

gas is commonly known as

wellhead gas.

Installation Items Needed

Before installing fireplace, make sure you have

the items listed below.

• external regulator for propane/LP unit only

(supplied by installer)

• piping (check local codes)

• sealant (resistant to propane/LP gas)

• equipment shutoff valve *

• test gauge connection *

• sediment trap (optional)

• tee joint

• pipe wrench

• approved flexible gas line with gas connector

(if allowed by local codes) (not provided)

* A CSA design-certified equipment shutoff valve

with 1/8" NPT tap is an acceptable alternative to

test gauge connection. Purchase the optional CSA

design-certified equipment shutoff valve from your

dealer. See Accessories, page 32.