For propane/LP units, the installer must supply

an external regulator. The external regulator will

reduce incoming gas pressure. You must reduce

incoming gas pressure to between 11" and 14" of

water. If you do not reduce incoming gas pres-

sure, heater regulator damage could occur. Install

external regulator with the vent pointing down

as shown in Figure 17. Pointing the vent down

protects it from freezing rain or sleet.

CAUTION: Use only new, black

iron or steel pipe. Internally-tinned

copper tubing may be used in cer-

tain areas. Check your local codes.

Use pipe of 1/2" diameter or greater

to allow proper gas volume to fire-

place. If pipe is too small, undue

loss of volume will occur.

Installation must include an equipment shutoff valve,

union, and plugged 1/8" NPT tap. Locate NPT tap

within reach for test gauge hook up. NPT tap must

be upstream from fireplace (see Figure 18).
IMPORTANT:

Install equipment shutoff valve in an

accessible location. The equipment shutoff valve is for

turning on or shutting off the gas to the appliance.

Check your building codes for any special re-

quirements for locating equipment shutoff valve

to fireplaces.

Apply pipe joint sealant lightly to male NPT threads.

This will prevent excess sealant from going into pipe.

Excess sealant in pipe could result in clogged fire-

place valves. Never use sealant on flare threads.

INSTALLATION

Continued

Figure 17 - External Regulator on

Propane/LP Supply Tank with Vent

Pointing Down

External
Regulator

Propane/LP
Supply Tank

Vent Pointing Down

* Purchase the optional CSA design-certified

equipment shutoff valve from your dealer. See

Accessories, page 32.

** Minimum inlet pressure for purpose of input

adjustment.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

We recommend that you install a sediment trap in

supply line as shown in Figure 18. Locate sediment

trap where it is within reach for cleaning. Install in

piping system between fuel supply and fireplace.

Locate sediment trap where trapped matter is not

likely to freeze. A sediment trap traps moisture

and contaminants. This keeps them from going

into fireplace gas controls. If sediment trap is not

installed or is installed wrong, fireplace may not

run properly.

Figure 18 - Gas Connection

3" Minimum

CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*

Natural Gas
From Gas
Meter
(5" W.C.** to
10.5" W.C.
Pressure)

Propane/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)

Sediment Trap

Cap

Pipe

Tee

Nipple Joint