Obtaining help information through the serial port, Obtaining a summary of all settings, Reclose and reset timer setting command – Basler Electric BE1-79A User Manual

Page 37

Advertising
background image

9310200990 Rev J

BE1-79A Communication Commands

4-3

For clarity in the examples, relay responses are printed in the

Courier typeface.

EXIT command example: exit after making setting changes.
EXIT

>SAVE CHANGES (Y/N/C)?

Prompt to save (Y)es, discard changes (N)o, or (C)ontinue

>Y

Confirmation to save changes

CHANGES SAVED

Confirmation that changes were saved

The HELP or H command provides general help information on command syntax and functionality when

the manual is not available. Help is available only when the relay is in a reset state.

Obtaining Help Information Through the Serial Port

HELP Command
Purpose:

Obtains help on using serial port commands.

Syntax:

HELP or H

Comments: The HELP command returns a listing of all available commands along with the proper

syntax for each command.

All relay settings may be listed using the S command.

Obtaining a Summary of All Settings

S Command
Purpose:

Read all relay settings back to user.

Syntax:

SP-79A[n]

Comments: S by itself may be used to read all relay settings. SP-79A[n] is used to read a specific

setting. the S command can be used to make a record of the relay settings after they have

been set.

S command example: Obtain a report of the relay settings.
A=

S

SP-79A1 5,10

SP-79A2 15,20

SP-79A3 25,30

SP-79A4 35,40

SP-79ALO 45,50

SP-79ARS D,0,5

SP-ALM 2

>

SP-79A Command

Reclose and Reset Timer Setting Command

Purpose:

Read or change the reclose and reset timer settings.

Syntax:

S[-79a[n][=<reclose time delay>,<reset time delay>]

Comments: n: reclose number of LO for lockout. See Table 4-1 for setting defaults.

reclose time delay: adjustable from 0 to 300 seconds in 0.1 second steps. A Reclose 1

setting of zero will cause an instantaneous first reclosure. A setting of zero for any other

reclose time delay will disable the reclose shot.
reset time delay: adjustable from 0 to 300 seconds in 0.1 second steps. A reset time delay

setting of zero will cause the reset to be disabled. A reset time delay setting less than the

reclose time setting will cause an immediate reset following the reclose attempt.

SP-79A command example: Read the second reclose and reset timer settings.
A=

SP-79A2

15.0,20.0

>

Advertising