Ds4(a)­rpc opening menu – BayTech DS2-RPC 2012 User Manual

Page 14

Advertising
background image

Page

14 

DS4(A)­RPC OPENING MENU 



















Figure 13: Admin User Configuration

Figure 14: Non-Admin User Configuration


















The unit displays a list of modules installed in the
DS4 chassis, not all available slots have to be filled.
Type “5” or whatever number list the “DS-RPC”,
and press ‘Enter’

Configuration
DS62 module #1..........1
DS74 module #2..........2
DS74 module #3..........3
DS74 module #4..........4
DS-RPC module #5..........5

NOTE: Module #1 in slot 1 is for the Host module. Module #2-4 in slots 2-4 are the DS74-
Peripheral module which connects to the external devices. Module #5 is the outlet module located
internal to the chassis. Refer to the individual Host and DS74 manuals to configure these modules.

With a valid connect to the host module; you should get
the following Host Module menu. Type “C” at the prompt
and press ‘Enter’ to display the module configuration
menu.

Module:
Attention Character: ;

Device A ................1
Device B ................2
Device C ................3
Device D ................4
DS-RPC ................5
Configure.......................C
Status..........................S
Unit Reset......................RU
Logout..........................T
Enter Request :c

NOTE: Only the Admin user assigned to the First position in the manage users menu will have
the following options available: ‘Config’, ‘Lock’, ‘Unlock’ and ‘Clear’.

On n <cr> --Turn on an Outlet, n=0,1...4,all
Off n <cr> --Turn off an Outlet, n=0,1...4,all
Reboot n <cr> --Reboot an Outlet, n=0,1...4,all
Status <cr> --DS-RPC Status

Config

<cr> --Enter configuration mode

Lock n

<cr> --Locks Outlet(s) state, n=0,1...4,all

Unlock n

<cr> --Unlock Outlet(s) state, n=0,1...4,all

Current <cr> --Display True RMS Current

Clear

<cr> --Reset the maximum detected current

Temp <cr> --Read current temperature
Voltage <cr> --Display True RMS Voltage
Logout <cr> --Logoff
Logoff <cr> --Logoff
Exit <cr> --Logoff
Password <cr> --Changes the current user password
Whoami <cr> --Displays the current user name
Unitid <cr> --Displays the unit ID
Help <cr> --This Command


Type "Help" for a list of commands

DS-RPC>

On n <cr> --Turn on an Outlet, n=0,1...4,all
Off n <cr> --Turn off an Outlet, n=0,1...4,all
Reboot n <cr> --Reboot an Outlet, n=0,1...4,all
Status <cr> --DS-RPC Status
Current <cr> --Display True RMS Current
Temp <cr> --Read current temperature
Voltage <cr> --Display True RMS Voltage
Logout <cr> --Logoff
Logoff <cr> --Logoff
Exit <cr> --Logoff
Password <cr> --Changes the current user password
Whoami <cr> --Displays the current user name
Unitid <cr> --Displays the unit ID
Help <cr> --This Command


Type "Help" for a list of commands

DS-RPC>

Advertising