BECKHOFF KL2521-0000 User Manual

Page 16

Advertising
background image

Access from the user program

14

KL2521


Examples for Register Communication

Example 1

Reading register 8 in the BK2000 with a Kl3022 and the end terminal.

If the following bytes are transferred from the controller to the terminal,

Byte

Byte3 Byte2 Byte1

Byte0

Name Data OUT, low byte Data OUT, high byte Not used

Control

Value 0xXX 0xXX 0xXX

0x88


the terminal returns the following type designation (0x0BCE corresponds to
the unsigned integer 3022).

Byte

Byte3 Byte2 Byte1

Byte0

Name Data IN, low byte

Data IN, high byte

Not used

Status

Value 0xCE 0x0B 0x00

0x88



Example 2

Writing register 31 in the BK2000 with an intelligent terminal and the end
terminal.

If the following bytes (user code word) are transferred from the controller to
the terminal,

Byte

Byte3 Byte2 Byte1

Byte0

Name

Data OUT, low byte Data OUT, high byte Not used

Control

Value

0x35 0x12 0xXX

0xDF


the user code word is set and the terminal returns the register address with
the bit 7 for register access and the acknowledgement.

Byte

Byte3 Byte2 Byte1

Byte0

Name

Data IN, low byte

Data IN, high byte

Not used

Status

Value

0x00 0x00 0x00

0x9F