Control and Status Byte

Control Byte in process data exchange

The Control Byte is sent to the terminal from the controller. It can be used
in register mode (REG = 1) or in process data exchange (REG = 0).

Bit

7 6 5 4

3 2 1 0

Name

Reg_Access 0

Cnt_Clr 0

0 Go_Counter

Ramp_Dis

Freq_Sel

Bit

Name

Function

7

Reg_Access

0: Register communication inactive (process data exchange)

5

Cnt_Clr

The contents of the counter is cleared or set (Feature.10) by this
bit. Any overflow or underflow bits that might be set are also
cleared by this bit. The process can be edge triggered or level
triggered (Feature.4).

2

Go_Counter

If travel distance control is active (Feature.9), then a pre-set
counter value is approached when the bit is set

1

Ramp_DisS

Operation of the ramp function is cancelled, in spite of Feature.5
being active; if travel distance control is active, it is interrupted by
this bit

0

Freq_Sel

Rapid change of the base frequency
(only if the ramp function is inactive)
0: Base frequency 1 (registers 36 / 37)
1: Base frequency 2 (registers 38 / 39)




Status Byte in process data exchange

The Status Byte is sent from the module to the controller.

Bit

7 6 5 4

3 2 1 0

Name

Reg_Access Error

Input_Z Input_T Overflow

Underflow

Ramp_Active

Sel_Ack/

End_Counter

Bit

Name

Function

7

Reg_Access

0: acknowledge for process data exchange

6

Error

General error bit, included with overflow/underflow

5

Input_Z

End position reached

4

Input_T

The actual value when the device is connected does not agree
with the set value of the connected device.

3

Overflow

This bit is set if the 16-bit counter overflows (65535 -> 0). It is
reset when the counter exceeds one third of its measuring range
(21845 -> 21846) or immediately an underflow occurs.

2

Underflow

This bit is set if the 16-bit counter underflows (0 -> 65535). It is
reset when the counter drops below two thirds of its measuring
range (43690 -> 43689) or immediately an overflow occurs.

1

Ramp_Active

Ramp is currently being followed

0

Sel_Ack/

End_Counter

Confirms the change of base frequency.
At

activated travel distance control:

target counter value reached



The change of the base frequency needs a reset for activation.