Technical data, Connection, Kl3311 – BECKHOFF KL3311 User Manual

Page 5

Advertising
background image

Technical data

KL3311, KL3312, KL3314 and KL3302

3


Technical data

Technical data

KL3311

KL3302*

KL3312

KL3314

Number of inputs

1

2

2

4

Power supply

via the K-Bus

Thermocouple sensor type

Types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement

Connection

2 wire

Temperature range

within the respective defined range of the sensor
(Default: type K; -100° ... 1370°C)

Resolution

0.1°C per digit

Broken lead detection

yes

no

yes

yes

Conversion time

~ 200 ms

~ 250 ms

Meas. error (total meas.

range)

< ± 0.5% (of the full scale value)

Electrical isolation

500 V

rms

(K-Bus/signal voltage)

Current consumption from

K-Bus

typically 65 mA

Bits width in process

image

Input: 1 x 16 bits of data
(1 x 8 bits control/status
optional)

Input: 2 x 16 bits of data
(2 x 8 bits control/status
optional)

Input: 4 x 16 bits of data
(4 x 8 bits control/status
optional)

Configuration

no address setting, configuration via bus coupler or controller

Weight

approx. 70 g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95 % no condensation

Vibration / shock

resistance

according to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29

EMC resistance burst / ESD

according to EN 61000-6-2 / EN 61000-6-4

Installation position

any

Protection class

IP20

*) KL3302 is no longer available and was replaced with KL3312.