3 terminal configuration, 2 technical data, 1 register overview – BECKHOFF KL6071 User Manual

Page 5

Advertising
background image

Terminal configuration

KL6071

3


2.2 Technical data

Product name

KL6071

Cut off frequency

10 kHz

Current consumption from K-Bus

typically 50 mA

Electrical isolation

500 V

rms

(K-Bus / field voltage)

Bit width in the input process image

5 Byte input data, 1 status byte

Bit width in the output process image

5 Byte output data, 1 control byte

Weight

app. 60 g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95%, no condensation

Vibration / Shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29

EMC resistance burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Installation position

any

Type of protection

IP20



3 Terminal configuration



3.1 Register overview

Register

Comment

Default value

R/W

Storage medium

R0

reserved

0x0000

R

...

...

...

...

...

R5

reserved

0x0000

R

R6

Diagnose-Register - not used

0x0000

R

R7

Command register - not used

0x0000

R

R8

Terminal type

6071

R

ROM

R9

Firmware-Version

0x????

R

ROM

R10

Multiplex shift register

0x0130

R

ROM

R11

Signal channels

0x0130

R

ROM

R12

minimum data length

0x3030

R

ROM

R13

Data structure

0x0000

R

ROM

R14

reserved

0x0000

R

R15

Alignment register

variable

R/W

RAM

R16

Hardware version

0x????

R/W

SEEROM

R17

reserved

0x0000

R/W

SEEROM

...

...

...

...

...

R30

reserved

0x0000

R/W

SEEROM

R31

Code-Wort-Register

variable

R/W

RAM

R32

Feature-Register

0x0000

R/W

SEEROM

R33

reserved

0x0000

R/W

SEEROM

...

...

...

...

...

R63

reserved

0x0000

R/W

SEEROM

Advertising