4 safety parameters, 5 dimensions – BECKHOFF EP1908 User Manual

Page 12

Advertising
background image

Product description

10

EP1908-0002

3.4 Safety parameters

Key figures

EP1908-0002

Lifetime [a]

20

Prooftest Intervall [a]

not required

1)

PFH

1.56E-09

%SIL3

1.56%

PFD

1.06E-04

%SIL3

10.59%

MTTFd [a]

>100

Performance level

PL e

Category

4

HFT

1

Element classification*

Type A

*) Classification according to EN 61508-2:2010 (see chapters 7.4.4.1.2 and 7.4.4.1.3)

The EP1908-0002 EtherCAT Box can be used for safety-related applications according to IEC 61508 up
to SIL3 and EN ISO 13849-1 up to PL e (Cat4).

1)

Special proof tests throughout the service life of the EtherCAT Box are not required.

3.5 Dimensions

The EP1908 module has the following dimensions.

Width: 30 mm
Height: 126 mm

Depth: 26.5 mm

When fully wired, the connected cables increase the total depth of the module.

Advertising