BECKHOFF EP1908 User Manual

Page 33

Advertising
background image

Operation

EP1908-0002

31

4.5.3.1

EP1908-0002 configuration for light barriers, light grids, light curtains, etc.

The EP1908-0002 also supports direct connection of contact-free protective devices with two self-testing
outputs such as light barriers, light grids, light curtains, laser scanners, etc.

CAUTION

Sensors with self-testing outputs

Only sensors with self-testing outputs and a maximum sensor self-test duration of
350 µs may be connected to the EP1908-0002.


Parameter
To connect these sensors please set the following parameters for the EP1908-0002 in the TwinCAT
System Manager:

•

Connect the two sensor signals either to channels 1, 2 & 3 and 4, 5 & 6 or channels 7 & 8 and
activate asynchronous repetition OSSD or any pulse repetition for the two inputs used under
parameter Logic for channel x and y. The difference between these settings is that with any pulse
repetition
simultaneous tests of the OSSD signals up to 350 µs are allowed.

•

For the two inputs used set the sensor test for the EL1908-0002 to false.

4.5.3.2

EP1908-0002 configuration for safety switching mats

The EP1908-0002 also supports direct connection of safety mats that operate based on the cross-circuit
principle.

Parameter
To connect these safety mats please set the following parameters for the EP1908-0002 in the TwinCAT
System Manager:

•

Connect the two sensor signals either to channels 1, 2 & 3 and 4, 5 & 6 or channels 7 & 8 and
activate the entry short cut channel x/y is no module fault for the two inputs used under
parameter Logic for channel x and y.

Advertising