BECKHOFF ILxxxx-B520 User Manual

Page 22

Advertising
background image

IO Data Mapping

19

ILxxxx-B520


2.3.1 Input Assembly



Default Instance

Number

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

111

0 to (n-1)

Analog Inputs

n to (m-1)

Digital Inputs

m

IL-Status Byte


Number

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

112

0 to (n-1)

Digital Inputs

n

IL-Status Byte


Number

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

113

0 to (n-1)

Analog Inputs

n

IL-Status Byte



2.3.2 Output Assembly



Default Instance

Number

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

101

0 to (n-1)

Analog Outputs

n to m

Digital Outputs


Number

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

102

n

Digital Outputs


Number

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

103

n

Analog Outputs



2.3.3 Mapping IO Assembly Data to DeviceNet Objects

Data Component Name 2.3.3.1.1.1 Class

Instance Attribute

Name

Number

Name

Number

Discrete Input n

Digital Input Channel

101

n

Value

1

Discrete Output n

Digital Output Channel

102

n

Value

1

Analog Input n

Analog Input Channel

103

n

Value

1

Analog Output n

Analog Output Channel

104

n

Value

1

IL-Status Byte

IL Config Object

100

1