3 il config object – BECKHOFF ILxxxx-B520 User Manual

Page 23

Advertising
background image

IL Config Object

ILxxxx-B520

20

3 IL Config Object

IL Config Object

The ILxxxx-B520 provides the vendor specific object class to access its
status, diagnostic and configuration data. Within the IL Config Object the
full range of Registers and Status-Information of the ILxxxx-B520 and the
connected extension boxes is available.

The IL Config Object Class is Vendor specific and within in the Range of
the Vendor specific Class Codes.



Class Code:

100 (64hex)


Class Attributes

Attribute

ID

Access

Rule

Name

Data

Type

Description

Semantics of

Value

1

Get

Revision

UINT

Revision of implementation

1

2

Get

Max. Instance

UINT

Max. number of instances

1



Instance Attributes

Attribute

ID

Access

Rule

Name

Data

Type

Description

Semantics of

Value

1

Get/Set

Terminal

Number

USINT

Number of terminal

0: Coupler
>0: Channels

2

Get/Set

Table Number USINT

Number of table

See ILxxxx-B520
/Channel Descrip-
tion

3

Get/Set

Register Num-

ber

USINT

Number of Register

See ILxxxx-B520
/Channel Descrip-
tion

4

Get/Set

Register Data DWORD

Register Value

see semantics

5

Get

IL-Status

BYTE

Status of the ILxxxx-B520 see semantics

6

Get

Extension Box-

Diagnosis

WORD

Diagnosis of the extension
boxes

see semantics

10

Get/Set IO Error Action BYTE

Action to be performed if a
fieldbus error occurs

see semantics

11

Get/Set

Poll produced

data type

BYTE

Type of IO data produced
via the Poll mode

see semantics

12

Get/Set

COS/ Cyclic

produced data

type

BYTE

Type of IO data produced
via the Change of State /
Cyclic mode

see semantics

13

Get/Set

Bit Strobe pro-

duced data

type

BYTE

Type of IO data produced
via the Bit Strobe / Cyclic
mode

see semantics

14

Get/Set

Poll / COS/
Cyclic con-

sumed data

type

BYTE

Type of IO data con-
sumed via the Poll /
Change of State / Cyclic
mode

see semantics

Advertising