BECKHOFF ILxxxx-B520 User Manual

Page 26

Advertising
background image

IL Config Object

23

ILxxxx-B520



IO Error Action

Note

Action to be performed if a fieldbus error occurred.

To activate a new IO error Action setting a device reset has to be per-
formed either by executing a power cycle to the ILxxxx-B520 or by
executing a Reset Service (Service Code 5) to the ILxxxx-B520 Iden-
tity Object (Class Id 1, Instance 1)

Value

Description

0

Leave local IO Cycle

1

Leave local IO Cycle and reset outputs (default)

2

freeze outputs




- Poll produced data type
- COS / Cyclic produced
data type
- Poll / COS / Cylic
consumed data type

Type of IO data produced/consumed via the Poll mode and Change of
State / Cyclic mode

Value

Description

0

Analog and digital IO Data with Status Byte (default)

1

Digital IO Data with Status Byte

2

Analog IO Data with Status Byte




- Bit Strobe produced
data type

Type of IO data produced via the Bit Strobe mode

Value

Description

0

Diagnostic Data (see Attribute extension box diagnosis)

1

Digital Inputs with Status Byte (default)




Device Diagnostics



Note

Enables Diagnostics of complex (analog/special function) extension boxes.
Setting this attribute enables the diagnosis of complex channels which is
needed to read the extension box diagnosis.

To activate the diagnosis functions a device reset has to be per-
formed either by executing a power cycle to the ILxxxx-B520 or exe-
cuting a Reset Service (Service Code 5)to the Identity Object (Class Id
1, Instance 1)

Value

Description

0

Device Diagnostic OFF (default)

1

Device Diagnostic ON