Air for combustion and ventilation – Desa CDCFPRA User Manual

Page 7

Advertising
background image

www.desatech.com

116658-01C

7

3. Add the Btu/Hr of all fuel burning appliances in

the space.

Vent-free fireplace

___________ Btu/Hr

Gas water heater*

___________ Btu/Hr

Gas furnace

___________ Btu/Hr

Vented gas heater

___________ Btu/Hr

Gas fireplace logs

___________ Btu/Hr

Other gas appliances* + __________ Btu/Hr

Total

= __________ Btu/Hr

* Do not include direct-vent gas appliances. Di-

rect-vent draws combustion air from the outdoors

and vents to the outdoors.

Example:

Gas water heater

_____________Btu/Hr

Vent-free fireplace

_____________Btu/Hr

Total

_____________Btu/Hr

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

_______ Btu/Hr (maximum the space can support)

_______ Btu/Hr (actual amount of Btu/Hr used)

Example:

35,840 Btu/Hr (maximum the space

can support)

40,000 Btu/Hr (actual amount of

Btu/Hr used)

The space in the above example is a confined space

because the actual Btu/Hr used is more than the maxi-

mum Btu/Hr the space can support. You must provide

additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an unconfined

space, remove door to adjoining room or add

ventilation grills between rooms. See Ventilation

Air From Inside Building, page 8.

B. Vent room directly to the outdoors. See Ventila-

tion Air From Outdoors, page 8.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr

the space can support, the space is an unconfined space.

You will need no additional fresh air ventilation.

WARNING: If the area in

which the fireplace may be oper-

ated is smaller than that defined

as an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

aiR FoR ComBUsTioN

aND VENTilaTioN

Continued

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA

54 defines a confined space as a space whose

volume is less than 50 cubic feet per 1,000 Btu

per hour (4.8 m

3

per kw) of the aggregate input

rating of all appliances installed in that space and

an unconfined space as a space whose volume is

not less than 50 cubic feet per 1,000 Btu per hour

(4.8 m

3

per kw) of the aggregate input rating of

all appliances installed in that space. Rooms com-

municating directly with the space in which the

appliances are installed*, through openings not

furnished with doors, are considered a part of the

unconfined space.

* Adjoining rooms are communicating only if

there are doorless passageways or ventilation grills

between them.

DETERMINING FRESH-AIR FLOW
FOR FIRePLACe LOCATION

Determining if you Have a Confined or
Unconfined Space

Use this work sheet to determine if you have a

confined or unconfined space.

Space:

Includes the room in which you will install

fireplace plus any adjoining rooms with doorless pas-

sageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x

width x height).

Length x Width x Height =__________cu. ft.

(volume of space)

Example:

Space size 16 ft. (length) x 14 ft.

(width) x 8 ft. (ceiling height) = 1792 cu. ft.

(volume of space)

If additional ventilation to adjoining room is

supplied with grills or openings, add the volume

of these rooms to the total volume of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

Example:

1792 cu. ft. (volume of space) x 20 =

35,840 (maximum Btu/Hr the space can support)

30,000

+ 10,000

= 40,000

Advertising