Installation, Continued, Mantel clearances – Desa FLAME-MAX UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER User Manual

Page 8

Advertising
background image

8

104256

UNVENTED PROPANE/LP GAS LOG HEATER

VANGUARD FLAME-MAX™

Figure 7 - Minimum Mantel Clearances When Using Hood

Minimum Non-
Combustible
Material

8"
Min.

12"

15"

18"

All minimum
distances are
in inches

Log Sets
18", 24", and
30" Models

20"

2

1

/2

"

6"

8"

10"

12"

Distances to
Underside of
Mantel

Hood
(GA6050, GA6052)

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

18”, 24”, 30”,
and 36”
Models

INSTALLATION

Continued

Figure 6 - Minimum Mantel Clearances Without Using Hood

Mantel Clearances

In addition to meeting non-combustible
material clearances, you must also meet
reaquired clearances between fireplace open-
ing and mantel shelf. If you do not meet the
clearances listed below, you will need a
hood.

Determing Minimum Mantel Clearance

If you meet minimum clearance between
mantel shelf and top of fireplace opening, a
hood is not required (see Figure 6).

Determining Minimum Mantel Clear-
ance When using a Hood

If your installation does not meet the above
minimum clearances, you must:

• operate the logs only with the flue

damper open, OR

• raise the mantel to an acceptable height,

OR

• remove the mantel.

Minimum Non-
Combustible
Material

Minimum Non-
Combustible
Material Height

Distances to
Underside of
Mantel

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

12"

8"

(A)

20"

14"

24

1/2

"

16

3/4

"

27

1/2

"

18

1/2

"

30"

20"

All minimum
distances are
in inches

Log Set
24"/30" Models

18" Model

2

1

/2

"

6"

8"

10"

24”/30”/36”
Models

Advertising