7 xr2500f standby battery calculations – DMP Electronics XR2500F User Manual

Page 25

Advertising
background image

XR2500F Installation Guide

Digital Monitoring Products

17

InstallatIon

11.7 XR2500F Standby Battery Calculations

Standby Battery Power Calculations

Standby Current

Alarm Current

XR2500F Control Panel

Relay Outputs 1-2 (ON)
Switch Grounds 3-6 (ON)
Active Zones 1-8
Active Zones 9-10
2-Wire Smoke Detectors
Panel Bell Output

Qty ___ 1_
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______

x
x
x
x
x
x

180mA

30mA

5mA

1.6mA

4mA

0.1mA

__180_mA
______
______
______
______
______

Qty ____1_
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______

x
x
x
x
x
x

180mA

30mA

5mA

*2mA
30mA

0.1mA

1500mA

__180_mA
______
______
______
______
______
______mA

893A Dual Phone Line Module

Qty ______

x

12mA ______

Qty ______

x

50mA ______

461 Interface Adaptor Card

7mA ______

x

7mA ______

462N Network Interface Card

Qty ______

x

50mA ______

Qty ______

x

50mA ______

462P Printer Interface Card

Qty ______

x

50mA ______

Qty ______

x

50mA ______

463G Digital Cellular Communicator Card

Qty _______

x

21mA ______

Qty _______

x

21mA ______

481 Expansion Interface Card

Qty ______

x

15mA ______

Qty ______

x

15mA ______

860 Relay Output Module (one relay active)

All four relays active

Qty _______

x

34mA

138mA

______

______

Qty _______

x

34mA

138mA

______

______

865 Style Y or Z Notification Module

Qty ______

x

26mA ______

Qty ______

x

85mA ______

866 Style W Notification Module

Qty ______

x

45mA ______

Qty ______

x

76mA ______

867 LX-Bus Style W Notification Module

Qty ______

x

30mA ______

Qty ______

x

86mA ______

630F Remote Fire Command Center

Qty ______

x

63mA ______

Qty ______

x

92mA ______

690 Security Command Keypad

Qty ______

x

77mA ______

Qty ______

x

84mA ______

693/793 Security Command Keypad

Active Zones (EOL Installed)

Qty ______

x

92mA

1.6mA

______
______

Qty ______
Qty ______

x
x

120mA

*2mA

______
______

790 Security Command Keypad

Active Zones (EOL Installed)

Qty ______

x

77mA

1.6mA

______
______

Qty ______
Qty ______

x
x

84mA
*2mA

______
______

7060/7060A/7160 Thinline Keypad

Qty ______

x

80mA ______

Qty ______

x

84mA ______

7063/7063A/7163 Thinline Keypad

Qty ______

x

86mA ______

Qty ______

x

112mA ______

7070/7070A/7170 Thinline Keypad

Active Zones (EOL Installed)

Qty ______

x

72mA

1.6mA

______
______

Qty ______
Qty ______

x
x

87mA
*2mA

______
______

7073/7073A/7173 Thinline Keypad

Active Zones (EOL Installed)

Qty ______

x

93mA

1.6mA

______
______

Qty ______
Qty ______

x
x

112mA

*2mA

______
______

733 Wiegand Interface Module

Active Zones (EOL Installed)
Annunciator (ON)

Qty ______
Qty ______

x
x

30mA

1.6mA

______
______

Qty ______
Qty ______
Qty ______

x
x
x

30mA
*2mA
20mA

______
______
______

734 Wiegand Interface Module

Active Zones (EOL Installed)
Annunciator (ON)

Qty ______
Qty ______

x
x

30mA

1.6mA

______
______

Qty ______
Qty ______
Qty ______

x
x
x

30mA
*2mA
20mA

______
______
______

Copy Sub-Totals to next page

Sub-Total Standby

*Based on 10% of active zones in alarm.

______mA

Sub-Total Alarm ______mA

Advertising