Dry Contact Relay Outputs

17.1 Description

The XR2500F panel provides two programmable auxiliary SPDT relays with the two DMP Model 305 relays in

K6 (Output 1) and K7 (Output 2) and a Model 431 Output Harness on the J2 6-pin Header. Each relay provides

one SPDT set of contacts that can be operated by any of the functions listed below:
1) Activation by zone condition: Steady, Pulsing, Momentary, and Follow
2) Activation by 24-hour 7-day schedule: One on and one off time a day for each relay
3) Manual activation from the Security Command keypad menu
4) Communication failure
5) Armed area annunciation
6) Fire Alarm, Fire Trouble, or Supervisory
7) Ambush Alarm
8) Exit and Entry timers
9) System Ready
10) Late to Close
Refer to the XR500 Series Programming Guide (LT-0679) for specific information.

17.2 Contact Rating

The Model 305 relay contacts are rated for 1 Amp at 30 VDC (allows .35 power factor). Connect auxiliary

power to the Relay Output 1 common terminal by installing the gray harness wire to terminal 7. Current

draw for all connected devices must not exceed the panel maximum current rating.

17.3 Output Harness Wiring

The Output Harness is pre-installed on the 6-pin header labeled J2. Output 2 uses the top three prongs,

and Output 1 uses the bottom three prongs. Outputs 1 and 2 are pre-wired to the 866 NAC modules located

within the XR2500F enclosure. For reference, the wire harness and contact locations are shown below:

Contact

Color

Output 1 normally closed

Violet

Output 1 common

Gray

Output 1 normally open

Orange

Output 2 normally closed

Blue

Output 2 common

White

Output 2 normally open

Yellow