1 mercantile, 2 entry delay, 3 exit delay – DMP Electronics XR2500F User Manual

Page 43: 5 bell, 7 wireless audible annunciation option, Access control system unitsansi/ul 294, 1 panel designation, 2 compatible devices, Ansi/ul 609, 4 bell

Advertising
background image

XR2500F Installation Guide

Digital Monitoring Products

35

CoMPlIanCe

Police Station Connected and Local Burglar Alarm Units

ANSI/UL 609

32.1 Mercantile

For Mercantile and Police Station Connect operation the Model XR500 Series must be mounted in an Attack

Resistant Housing, (DMP Model 350A or 350H).

32.2 Entry Delay

The maximum entry delay used must not be more than 60 seconds when using the Model 350A or 350H housing.

32.3 Exit Delay

The maximum exit delay used must not be more than 60 seconds.

32.4 Bell

A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
In a mercantile burglar alarm system, a mercantile alarm sounding device located within a building but outside

the protected area, is acceptable, provided it is rated for outside service and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency having jurisdiction over the protected property or
b) A central station or residential monitoring station complying with the Standard for Central Station Alarm

Services, UL 827.
In a mercantile burglar alarm system, an alarm sounding device located within the area of greatest

protection, or outside the area of greatest protection but within an area protected by an alarm system and

that shares a common control unit with the system installed in the area of greatest protection, is acceptable

provided it is rated for inside service and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency having jurisdiction over the protected property or
b) A central station or residential monitoring station complying with the Standard for Central Station Alarm

Services, UL 827.
An inside sounding device shall be mounted at least 10 feet (3.05 m) above the floor or at the surface of the

ceiling. When there is fixed construction within the area that could provide access for an intruder, the alarm

sounding device shall also be mounted at least 4 feet (1.2 m), as measured horizontally, away from the

edges of the fixed construction or at least 10 feet (3.05 m) above it so as to minimize access by an intruder.

32.5 Wireless Audible Annunciation Option

The Wireless Audible option must be selected as ANY for commercial applications.

Access Control System Units

ANSI/UL 294

33.1 Panel Designation

The XR2500F is designated as a stand alone unit.

33.2 Compatible Devices

The following devices are compatible with the XR2500F panels.

Access Control
733 Wiegand Interface Module

Proximity reader connector

734 Wiegand Interface Module

Programmable proximity reader connector

OP-08CB Motion Detector

Infrared sensor.

* PB-2 REX Button

Exit control push button

PP-6005B Proxpoint Plus® Reader

Proximity reader

MP-5365 Miniprox® Reader

Slimline proximity reader

PR-5455 ProxPro® II Reader

Long range reader with sounder

MX-5375 Maxi-Prox™ Reader

Long range reader compatible with 1351 Prox Pass

* This device has not been investigated and shall not be used in listed installations.