Installation, Continued – Desa VRL30PT User Manual

Page 9

Advertising
background image

110021-01A

For more information, visit www.desatech.com

For more information, visit www.desatech.com

9

9

Heat Resistant
Material

(A)

Carefully follow the instructions below. This will ensure safe
installation into a masonry, UL127-listed manufactured fireplace,
or listed vent-free firebox.

Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling

A. Clearances from the side of the fireplace cabinet to any com-

bustible material and wall should follow diagram in Figure 4.

Example:

The face of a mantel, bookshelf, etc. is made of

combustible material and protrudes 3

1

/

2

" from the wall. This

combustible material must be 4" from the side of the fireplace
cabinet (see Figure 4).

Note:

When installing your gas logs into a manufactured firebox,

follow firebox manufacturer’s instructions for minimum clear-
ances to combustible materials.

B. Clearances from the top of the fireplace opening to the ceiling

should not be less than 42 inches.

Figure 4 - Minimum Clearance for Combustible to Wall

*Minimum 16 inches from Side Wall

*

Example

INSTALLATION

Continued

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.)
Above Fireplace

Noncombustible

Requirements for

Material Distance (A)

Safe Installation

12" or more

Noncombustible material OK.

Between 8" and 12"

24" or 30" Models: Install
fireplace hood accessory
(GA6050, GA6052, or
GA6053 see

Accessories,

page 34).

Less than 8"

Noncombustible material
must be extended to at least
8". See

Between 8" and 12",

above. If you cannot extend
material, you must operate
heater with flue damper open.

Minimum Noncombustible Material Clearances

If Not Using Mantel

Note:

If using a mantel proceed to

If Using Mantel

. If not using a

mantel, follow the information on this page.

You must have noncombustible material(s) above the fireplace
opening. Noncombustible materials (such as slate, marble, tile, etc.)
must be at least 1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombustible material must
extend at least 8" up (for all models). If noncombustible material is
less than 12", you must install the fireplace hood accessory (24" and
30" models only). See Figure 5 for minimum clearances.

NOTICE: Manual control heaters may be used as a
vented product. If so, you must always run heater with
chimney flue damper open. If running heater with
damper open, noncombustible material above fire-
place opening is not needed. Go to

Installing Damper

Clamp Accessory for Vented Operation, page 11.

If Using Mantel

You must have noncombustible material(s) above the fireplace
opening. Noncombustible materials (such as slate, marble, tile, etc.)
must be at least 1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombustible material must
extend at least 8 inches up. If noncombustible material is less than
12", you must install the fireplace hood accessory. Even if noncom-
bustible material is more than 12", you may need the hood accessory
to deflect heat away from your mantel shelf. See Figure 5 and
Figures 6 and 7, page 10, for minimum clearances.

IMPORTANT:

If you cannot meet these minimum clearances, you

must operate heater with chimney flue damper open. Go to Install-
ing Damper Clamp Accessory for Vented Operation
, page 11.

INSTALLATION

Installation and Clearances For Vent-Free Operation (Cont.)

Advertising
This manual is related to the following products: