Operational recommendations – Flowserve V-370 R3 Edward Valves User Manual

Page 19

Advertising
background image

EDWARD UNIVALVE USER INSTRUCTIONS ENGLISH 12-13

19

OPERATIONAL RECOMMENDATIONS

RECOMMENDED CLOSING TORQUES
To assure long seat life and seat tightness, it is very

important to close the Univalve with enough seat

stress/stem load.
The torques in this table should be applied when closing

against the maximum (100°F) valve pressure. The impactor

handle/handwheel performance chart on pg. 20 will achieve

these stem loads.
Overtorquing can, on the other hand, damage seats and

bend stems, so torques greatly in excess of these should

not be applied.

Torques are for valves with stem packing tightened – see page 17.

Figure Number

All Valves With Five-Digit Figure Numbers

1/2

3/4

1

1-1/4

1-1/2

2

2-1/2

3

4

36120, 36124,
36128, 36160
36164, 36168

30

30

30

95

95

155

275

275

275

36220, 36224,
36228, 36260,
36264, 36268

30

30

30

95

95

155

275

275

275

66120, 66124,
66128, 66160,
66164, 66168

45

45

45

85

85

230

395

395

395

66220, 66224,
66228, 66260,
66264, 66268

45

45

45

85

85

230

395

395

395

96124, 96128,
96164, 96168

70

70

70

70

70

350

350

350

350

96224, 96228,
96264, 96268

70

70

70

70

70

350

350

350

350

MINIMUM TORQUE FOR CLOSING VALVES — FT-LB ON MAIN SEAT

(Do Not Apply This Load to Backseats.)

Advertising