Mask Command Frequency Warning, Command Frequency
Alarm, Command Amplitude Warning, Command Amplitude
Alarm, Position Frequency Warning, Position Frequency
Alarm, Position Amplitude Warning, and Position Amplitude
Alarm.

4.3.2.15

Inner Loop Status

Mask Pilot Relay Response Warning, Pilot Relay Response
Alarm, Piezo Voltage High Warning, Piezo Voltage High
Alarm, Piezo Voltage Low Warning, Piezo Voltage Low
Alarm, and Driver Module Alarm.

4.3.2.16

Main Board Status

Mask Main Board Electronic Failure Warning, Software Error
Warning, Memory Error Warning, Temperature High
Warning, and Temperature Low Warning.

4.3.2.17

Electronic Board Status

Mask Aux Card 1 Failure Warning, Aux Card 2 Failure
Warning, Aux Card 1 No Loop Power, Aux Card 2 No Loop
Power, Aux Card 1 Error, Aux Card 2 Error, Pressure Sensor
Board Failure Warning, and Low Battery Warning.

4.3.2.18

Stroke/Friction status

Mask Reversed Spring, Insufficient Spring, and No Spring.

4.3.2.19

Main Board Status

Mask Humidity Sensor Failure, Oscillator Fault, Position
Sensor ADC Failure, Supply Voltage Error, Reference
Voltage Error, Shunt Voltage Error, and Piezo Voltage Error.

4.3.2.20

Electrical Components Status

Mask Pilot Can't Open, Pilot Can't Shut, Hall Sensor Failure,
and ILO Out Of Range.

4.3.2.21

Software Status

Mask NVMEM CRC Error, RAM Error, RAM CRC Error,
FLASH CRC Error, Watch Dog Time Out, Stack Overflow
Warning, CPU Usage Warning, and Firmware Update
Applied.

4.3.2.22

Pressure Calibration Status

Mask Port S Out Of Range, Port A Out Of Range, Port B Out
Of Range, Port S Range too Small, Port A Range too Small,
Port B Range too Small, and Pressure Sensor Failure.

5 STROKE TESTS

Run a partial stroke tests and view results. Configure the
continuous stroke test.

DANGER: Using this feature will result in valve movement

and the inability to operate the valve until the operation is
complete. Notify proper personnel that the valve may
stroke, and make sure the valve is properly isolated before
proceeding.

5.1

Partial Stroke Test

Run a partial stroke tests and view results.

5.1.1

Run Partial Stroke Test

Start a partial stroke test. Warning: The PST will cause valve
movement.

5.1.2

PST Time To Breakaway

View the time required for the valve to begin movement.

5.1.3

PST Force at Breakaway

View the force recorded when the valve began to move. This
force is valid for slow ramps only.

5.1.4

PST Time to Target

View the time taken for the position to come within 2% of the
final command after the initial change in command.

5.1.5

PST Result

View the pass/fail result of the last partial stroke test.

5.2

Continuous Stroke Test

Configure the continuous stroke test (CST). This feature is
NOT recommended for processes requiring highly accurate
positioning, or for valves that are frequently adjusting
position. The CST function superimposes a small,
continuous bi-directional ramp over the input command. By
constantly moving the valve, additional diagnostic data can
be gathered that would otherwise be unavailable with a
constant input command. The superimposed ramp reverses
when the valve moves.

5.2.1

CST Ramp Rate

Set the rate of the superimposed ramp in percent/second.

5.2.2

CST Max Amplitude

Set the maximum ramp amplitude. The valve position will not
always follow the full ramp amplitude. If the valve moves
before the full ramp amplitude is reached, the superimposed
ramp command will be reversed, edging the valve the other
way. This way the actual movement of the valve is
minimized.

5.2.3

CST Interval

Set the amount of time (in seconds) the positioner should
wait between ramping attempts.

5.2.4

CST Failure Count